3 Functions

3.15Automatic restart

Parameter range:

P1210

 

P1211

Warnings

A0571

Faults

F0035

Function chart number:

-

After a power failure (F0003 "Undervoltage"), the "Automatic restart" function (enabled using P1210) automatically powers-up the drive inverter again. Any faults are automatically acknowledged by the drive inverter.

When it comes to power failures (line supply failure), then a differentiation is made between the following conditions:

Line undervoltage (brownout)

"Line undervoltage" is a situation where the line supply is interrupted and returns before (if installed) the BOP display has gone dark (this is an extremely short line supply interruption where the DC link hasn't completely collapsed).

Line failure (blackout)

"Line failure" is a situation where the display has gone dark (this represents a longer line supply interruption where the DC link has completely collapsed) before the line supply returns.

The automatic restart function P1210 is shown in the following diagram (refer to Table 3-22) as a function of external states / events.

Table 3-22 Automatic restarts

P1210

 

ON always active (permanent)

 

ON in no-voltage condition

 

Fault F0003 on

 

All other faults on

All faults on

 

No faults on

 

 

 

 

Blackout

Brownout

 

Blackout

Brownout

Blackout

 

 

Blackout

0

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Fault acknowl.

 

Fault acknowl.

Fault acknowl.

 

 

 

 

 

 

 

 

 

 

 

 

2

Fault acknowl.

 

 

 

 

 

+

 

 

 

Restart

 

restart

 

 

 

 

 

 

 

 

3

Fault acknowl.

Fault acknowl.

 

Fault acknowl.

Fault acknowl.

Fault acknowl.

 

 

+

+

 

+

+

+

 

 

 

restart

restart

 

restart

restart

restart

 

 

 

4

Fault acknowl.

Fault acknowl.

 

 

 

+

+

 

 

 

 

restart

restart

 

 

 

 

 

 

 

5

Fault acknowl.

 

Fault acknowl.

Fault acknowl.

 

 

 

+

 

+

+

 

 

Restart

 

restart

 

 

restart

 

restart

 

 

 

6

Fault acknowl.

Fault acknowl.

 

Fault acknowl.

Fault acknowl.

Fault acknowl.

 

 

Restart

+

+

 

+

+

+

 

 

 

restart

restart

 

restart

restart

restart

 

 

 

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

127

Page 127
Image 127
Siemens 420 manual Automatic restart, Line undervoltage brownout, Line failure blackout, Blackout Brownout