Siemens 420 manual 10 JOG, JOG counter-clockwise and JOG clockwise

Models: 420

1 190
Download 190 pages 14.8 Kb
Page 104
Image 104

3 Functions

Issue 07/04

3.10JOG

Parameter range:

P1055 – P1061

Warnings

A0923

Faults

-

Function chart number:

FP5000

The JOG function is used as follows:

To check the functionality of the motor and drive inverter after commissioning has been completed (the first traversing motion, checking the direction of rotation, etc.)

Positioning a drive / a driven load into a specific position Traversing a drive, e.g. after a program has been interrupted

The drive is traversed using this function by entering fixed frequencies P1058, P1059. The JOG mode can be selected either using the operator panel (refer to Section 3.1.3), digital inputs or also via the serial interfaces (refer to the example). An ON/OFF command is not used to move the drive, but when the "JOG keys" are pressed. These "JOG keys" are selected using the BICO parameters P1055 and P1056.

 

 

 

 

 

 

A0923

A0923

 

 

"1"

 

 

 

 

 

DIN

JOG right

 

 

 

 

t

 

P1055

"0"

 

 

 

 

 

BOP

 

(0)

 

 

 

 

 

 

 

 

 

 

 

 

USS

 

"1"

 

 

 

 

 

JOG left

 

 

 

 

 

BOP link

 

 

 

 

t

P1056

"0"

 

 

 

 

USS

 

 

 

 

 

 

(0)

f

 

 

 

 

COM link

 

P1082

 

 

 

 

CB

 

 

 

 

 

 

 

P1058

 

 

 

 

 

COM link

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

P1059

P1060

P1061

P1060

P1061

 

 

 

-P1082

 

 

 

 

 

Fig. 3-35 JOG counter-clockwise and JOG clockwise

MICROMASTER 420

Operating Instructions

104

6SE6400-5AA00-0BP0

Page 104
Image 104
Siemens 420 manual 10 JOG, JOG counter-clockwise and JOG clockwise