3 Functions

Issue 07/04

3.12.2Ramp-function generator (RFG)

Parameter range:

P1120, P1121

 

r1119, r1170

 

P1130 – P1142

Warnings

-

Faults

-

Function chart number:

FP5000, FP5300

The ramp-function generator is used to limit the acceleration when the setpoint changes according to a step function. This therefore helps to reduce the stressing on the mechanical system of the machine. An acceleration ramp and a braking ramp can be set independently of one another using the ramp-up time P1120 and the ramp-down time P1121. This allows a controlled transition when the setpoint is changed (refer to Fig. 3-42).

 

f

 

 

 

roundingWithout

fmax

 

 

 

f2

 

 

 

 

 

 

 

 

f1

P1120

P1121

t

 

 

 

 

f

 

 

 

 

fmax

 

 

 

 

f2

 

 

 

With rounding

f1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1130

tup

 

 

P1131

 

 

 

 

 

 

P1132

 

tdown

P1133

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

f 2

- f1

 

 

P1120

 

1

(P1130

+ P1131)

 

 

 

 

 

 

 

for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P1082

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tup

=

 

1

(P1130 + P1131) +

 

f 2 - f

1

P1120

 

 

 

 

 

 

 

 

 

2

 

P1082

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for

 

f 2

- f1

 

 

P1121

 

1

(P1132

+ P1133)

 

 

 

 

 

 

 

 

 

 

P1082

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tdown =

 

1

(P1132

+ P1133) +

 

f 2

- f1

 

P1121

 

 

 

 

 

 

 

 

 

2

P1082

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 3-42 Ramp-function generator

MICROMASTER 420

Operating Instructions

112

6SE6400-5AA00-0BP0

Page 112
Image 112
Siemens 420 manual Ramp-function generator RFG, With rounding