3 Functions

3.5.5.2

Selection of command source

P0700 =...

Selection of

2

command source

 

Selects digital command source.

0Factory fault setting

1BOP (keypad)

2Terminal

4USS on BOP link

5USS on COM link

6CB on COM link

BOP

 

 

 

 

 

Terminals

 

 

P0700 = 2

 

USS

BOP link

 

 

 

USS

 

COM link

 

 

 

CB

 

COM link

 

Sequence control

Setpoint

 

 

Motor

channel

 

 

control

 

 

 

 

 

 

3.5.5.3Digital input (DIN)

P0701=...

P0702 =...

P0703 =...

P0704 = 0

P0724 =...

Function of digital input 1

1

Terminal 5

 

1

ON / OFF1

 

 

 

Function digital input 2

12

Terminal 6

 

12

Reverse

 

Function digital input 3

9

Terminal 7

 

9

Fault acknowledge

 

 

 

Function digital input 4

0

Via analog input

 

Terminals 3, 4

 

0

Digital input disabled

 

Debounce time for

3

digital inputs

 

Defines debounce time (filtering time) used for digital inputs.

0No debounce time

12.5 ms debounce time

28.2 ms debounce time

312.3 ms debounce time

Possible Settings:

0Digital input disabled

1ON / OFF1

2ON + Reverse / OFF1

3OFF2 – coast to standstill

4OFF3 – quick ramp-down

9Fault acknowledge

10JOG right

11JOG left

12Reverse

13MOP up (increase frequency)

14MOP down (decrease frequency)

15Fixed setpoint (Direct selection)

16Fixed setpoint (Direct selection + ON)

17Fixed setpoint (Binary coded selection + ON)

21Local/remote

25DC brake enable

29External trip

33Disable additional freq setpoint

99Enable BICO parameterization

DIN channel

Kl.8

P24

Debounce time: DIN

 

 

Kl.9

0 V

0 ... 3

 

 

 

P0724 (3)

 

 

 

 

24 V

 

 

 

 

 

 

T 0

 

 

 

 

&

0 V

Function of DIN 1

0 ... 99

P0701 (1)

0

Function

...

99

 

r0722

r0722 CO/BO: Bin.inp.val