3 Functions

Issue 07/04

3.9Motorized potentiometer (MOP)

Parameter range:

P1031 – r1050

Warnings

-

Faults

-

Function chart number:

FP3100

This function emulates an electromechanical potentiometer to enter setpoints. The motorized potentiometer value is adjusted using the "Raise" and "Lower control signal" which is selected using BICO parameters P1035 and P1036 (refer to Fig.

3-34). The value which has been set is available through connector output r1050 so that it can be further connected and used.

DIN

 

"1"

 

 

P0840

"0"

 

 

 

 

t

BOP

 

 

 

 

"1"

 

 

 

 

 

 

USS

P1035

"0"

 

t

 

 

BOP link

 

 

 

 

"1"

 

 

USS

 

 

 

P1036

"0"

 

 

COM link

 

t

CB

 

 

 

 

f

 

 

COM link

 

 

 

 

P1082

 

 

 

 

 

 

 

 

P1080

 

 

 

 

P1120

P1121

t

 

 

 

 

 

-P1080

 

 

 

 

 

r1050

fact

 

 

-P1082

 

 

 

 

 

Fig. 3-34 Motorized potentiometer

Selecting via serial interfaces

The MOP functionality can be selected via the operator panels (refer to Section 3.1.3), digital inputs as well as via serial interfaces (refer to the example). Parameterization is also possible directly using BICO parameters P1035 and P1036 as well as also parameters P0700 and P0719. In this case, for a value assigned to P0700, the BICO parameter is appropriately modified.

Example: Command source via "USS on BOP link" interface

a) Standard method

P0700

= 4

b) BICO method

P1035

= 2032.13

 

 

P1036

= 2032.14

 

 

::::

 

 

 

(refer to P0700 for a complete list)

MICROMASTER 420

Operating Instructions

102

6SE6400-5AA00-0BP0

Page 102
Image 102