Siemens 420 manual Selection of command source, Selection of frequency setpoint, Min. frequency

Models: 420

1 190
Download 190 pages 14.8 Kb
Page 64
Image 64

3 Functions

Issue 07/04

P0700 =...

P1000 =...

P1080 =...

P1082 =...

P1120 =...

P1121 =...

P1135 =...

P1300 =...

P3900 = 1

ENDE

Selection of command source

2

0Factory default setting

1BOP (keypad)

2Terminal

4USS on BOP link

5USS on COM link

6CB on COM link

Selection of frequency setpoint

2

1MOP setpoint

2Analog setpoint

3Fixed frequency

4USS on BOP link

5USS on COM link

6CB on COM link

Min. frequency

0.00 Hz

(enters the minimum motor frequency in Hz)

Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation.

Max. frequency

50.00 Hz

(enters the maximum motor frequency in Hz)

Sets maximum motor frequency at which motor will run irrespective of the frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation.

Ramp-up time

10.00 s

(enters the ramp-up time in s)

Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no rounding is used.

Ramp-down time

10.00 s

(enters the deceleration time in s)

Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no rounding is used

OFF3 ramp-down time

5.00 s

(enters the fast stop ramp-down time in s)

Defines ramp-down time from maximum frequency to standstill for OFF3 command.

Control mode

0

(enters the required control mode)

 

0

V/f with linear characteristic

 

1

V/f with FCC

 

2

V/f with parabolic characteristic

 

3

V/f with programmable characteristic

 

End of quick commissioning

0

(start of the motor calculation)

 

0No quick commissioning (no motor calculations)

1Start quick commissioning with factory reset

2Start quick commissioning

3Start quick commissioning only for motor data

NOTE

For P3900 = 1,2,3 P0340 is internally set to 1 and the appropriate data calculated (refer to the parameter list P0340).

End of quick commissioning/ drive setting

If additional functions must be implemented at the drive inverter, please use the instructions in Section 3.5.5 "Commissioning the application". We recommend this procedure for drives with a high dynamic response..

MICROMASTER 420

Operating Instructions

64

6SE6400-5AA00-0BP0

Page 64