3.1.2Interconnecting signals (BICO technology)

A state-of-the-art drive unit must be able to interconnect internal and external signals (setpoint / actual values and control / status signal). This interconnection functionality must have a high degree of flexibility in order to be able to adapt the drive to new applications. Further, a high degree of usability is required, which also fulfills standard applications. This is the reason that within the MICROMASTER series of drive units, BICO technology (flexibility) and fast parameterization using parameters P0700 / P1000 (usability) or P0719 (combination P0700/P1000) have been introduced to be able to fulfill both of these requirements.

3.1.2.1Selecting the command source P0700 / selecting the setpoint source P1000

The following parameters can be used to quickly interconnect setpoints and control signals:

P0700 "Selection of command source"

P1000 "Selection of setpoint source"

These parameters are used to define via which interface the drive inverter receives the setpoint or the power-on/power-off command. The interfaces, listed in Table 3-2 can be selected for the command source P0700.

Table 3-2

Parameter P0700

 

 

Parameter values

Significance / command source

0

 

Factory default

1

 

BOP (operator panel, refer to Section 3.2.1)

 

 

 

2

 

Terminal strip

 

 

 

4

 

USS on BOP link

 

 

 

5

 

USS on COM link

6

 

CB on COM link

 

 

 

The following internal or external sources / interfaces can be selected for the frequency setpoint source P1000. In addition to the main setpoint (1st position), a supplementary setpoint (2nd position) can be selected (refer to Table 3-3).