3 Functions

3.14.2Compound braking

Parameter range:

P1236

Warnings

-

Faults

-

Function chart number:

-

For compound braking (this is enabled using P1236) DC braking is superimposed with regenerative braking (where the drive regenerates into the line supply as it brakes along a ramp). If the DC link voltage exceeds the compound switch-in threshold VDC-Comp(refer to Fig. 3-53), then a DC current is impressed as a function of P1236. In this case, braking is possible with a controlled motor frequency and minimum regenerative feedback. Effective braking is obtained without having to use additional components by optimizing the ramp-down time (P1121 for OFF1 or when braking from f1 to f2, P1135 for OFF3) and using compound braking P1236.

Compound braking is suitable for:

Horizontal motion (e.g. traversing drives, conveyor belts) Vertical motion (e.g. hoisting gear)

 

P1236 = 0

 

 

P1236 >0

 

 

Without Compound braking

 

 

With Compound braking

f

f_set

f

 

f_set

 

 

 

 

 

 

f_act

 

 

f_act

 

 

t

 

 

 

t

 

i

i

 

 

 

 

t

 

 

 

t

u

 

u

 

 

 

DC-link

DC-link

 

 

 

UDC-Comp

 

 

 

 

t

 

 

 

t

 

 

P1254 = 0 :

UDC-Comp = 1.13

2 P0210

 

 

P1254

0 :

UDC-Comp= 0.98 r1242

Fig. 3-53 Compound braking

The compound braking switch-in threshold VDC-Compis calculated as a function of parameter P1254 (Auto detect VDC switch-on levels) either directly using the line supply voltage P0210 or indirectly using the DC link voltage and r1242 (refer to the formula in Fig. 3-53).

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

125

Page 125
Image 125