3 Functions

3.20Power module protection

3.20.1General overload monitoring

Parameter range:

P0640, r0067, r1242, P0210

Warnings

A0501, A0502, A0503

Faults

F0001, F0002, F0003

Function chart number:

-

Just the same as for motor protection, MICROMASTER provides extensive protection for the power components. This protection concept is also sub-divided into 2 levels:

Warning and response Fault and shutdown

Using this concept, a high utilization of the power module components can be achieved without the drive inverter being immediately shut down. The power module components are monitored as follows:

Table 3-26 General protection of the power components

 

Warning and response

Fault and shutdown

Overcurrent / short circuit

Imax controller for V/f

F0001

 

A0501

 

 

r0056 bit 09

 

 

r0056 bit 13

 

 

(refer to Section 3.21.1.2)

 

 

 

 

DC link overvoltage

Vdc_max controller

F0002

 

A0502

 

 

(refer to Section 3.17.1)

 

The monitoring thresholds for the right-hand column in the table above are permanently saved in the drive inverter and cannot be changed by the user. On the other hand, the threshold levels for the "Warning and response" column can be modified by the user to optimize the system. These values have default settings so that the "Fault and shutdown" thresholds do not respond.