5 MICROMASTER 420 specifications

Issue 07/04

Table 5-4 MICROMASTER 420 Specifications

In order to have a UL compliant installation fuses from the SITOR range with the appropriate current rating must be used.

Input voltage range

1 AC 200 V – 240 V, ± 10 %

 

 

 

 

 

(with built in Class A Filter)

 

 

 

 

 

 

 

 

Order No.

6SE6420-

2AB11

2AB12

2AB13

2AB15

2AB17

2AB21

2AB21

2AB22

2AB23

 

 

 

-2AA1

-5AA1

-7AA1

-5AA1

-5AA1

-1BA1

-5BA1

-2BA1

-0CA1

Output Rating

 

[kW]

0.12

0.25

0.37

0.55

0.75

1.1

1.5

2.2

3.0

 

[hp]

0.16

0.33

0.5

0.75

1.0

1.5

2.0

3.0

4.0

 

 

Output Power

 

[kVA]

0.4

0.7

1.0

1.3

1.7

2.4

3.2

4.6

6.0

 

 

 

 

 

 

 

 

 

 

 

 

Input Current 1)

 

[A]

1.8

3.2

4.6

6.2

8.2

11.0

14.4

20.2

35.5

Output Current

 

[A]

0.9

1.7

2.3

3.0

3.9

5.5

7.4

10.4

13.6

Fuse

 

[A]

10

10

10

10

16

20

20

32

40

 

 

 

 

 

 

 

 

 

 

 

 

Recommended

 

3NA

3803

3803

3803

3803

3805

3807

3807

3812

3817

For UL specified

 

 

 

 

 

 

 

 

 

 

 

 

 

*

*

*

*

*

*

*

*

*

 

 

 

Input Cable, min.

 

[mm2]

1.0

1.0

1.0

1.0

1.0

2.5

2.5

4.0

6.0

 

[awg]

17

17

17

17

17

15

15

11

9

 

 

Input Cable, max.

 

[mm2]

2.5

2.5

2.5

2.5

2.5

6.0

6.0

6.0

10.0

 

[awg]

13

13

13

13

13

9

9

9

7

 

 

Output Cable, min.

 

[mm2]

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.5

 

[awg]

17

17

17

17

17

17

17

17

15

 

 

Output Cable, max.

 

[mm2]

2.5

2.5

2.5

2.5

2.5

6.0

6.0

6.0

10.0

 

[awg]

13

13

13

13

13

9

9

9

7

 

 

Weight

 

[kg]

1.2

1.2

1.2

1.3

1.3

3.3

3.6

3.6

5.2

 

[lbs]

2.6

2.6

2.6

2.9

2.9

7.3

7.9

7.9

11.4

 

 

1)Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line supply Vk = 1 % referred to the rated drive converter power and a rated line supply voltage of 240 V without line commutating reactor. If a line commutating reactor is used, the specified values are reduced by between 55 % and 70 %.

*UL listed fuses such as Class NON from Bussmann are required for use in America

MICROMASTER 420

Operating Instructions

160

6SE6400-5AA00-0BP0

Page 160