3 Functions

3.11.2PID fixed setpoint (PID-FF)

Number:

7

Parameter range:

P2201 – r2224

Warnings

-

Faults

-

Function chart number:

FP3300, FP3310

Analog to the fixed frequencies (refer to Section 3.8), the PID controller has separate programmable PID fixed setpoints. The values are defined using parameters P2201 – P2207 and are selected using binector inputs P2220 – P2222. The selected PID fixed setpoint is available via connector output r2224 where it can be further processed (e.g. as PID main setpoint P2253 = 2224).

3 methods are available to select the PID fixed setpoints, analog to the fixed frequencies (Section 3.8):

Direct selection

Direct selection + ON command Binary-coded selection + ON command

The methods are selected using parameters P2216 – P2218.

P0701 = 15

 

 

 

 

or

 

 

 

 

P0701 = 99, P2220 = 722.0, P2216 = 1

 

 

 

 

P2220

 

1

 

DIN1

r0722.0

 

. . . .

 

 

0

 

 

 

2,3

 

 

 

 

 

 

. .

 

0

 

 

. .

 

 

 

 

P2201

 

 

 

 

 

 

 

 

. . . .

r2224

Fig. 3-38 Example to directly select the PID fixed frequency of fixed frequency 1 via DIN1

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

109