3 Functions

Issue 07/04

3.5.5.8Motor potentiometer (MOP)

P1031 =...

P1032 =...

P1040 =...

Setpoint memory of the MOP

0

Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down.

0 MOP setpoint will not be stored

1 MOP setpoint will be stored (P1040 is updated)

Inhibit negative MOP setpoints

1

0

Neg. MOP setpoint is allowed

 

1

Neg. MOP setpoint inhibited

 

 

 

Setpoint of the MOP

5.00 Hz

Determines setpoint for motor potentiometer control.

 

MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121.

Possible parameter settings for the selection of MOP:

 

 

 

 

 

 

Selection

MOP up

MOP down

DIN

P0719 = 0, P0700 = 2, P1000 = 1

P0702 = 13

P0703 = 14

or

(DIN2)

(DIN3)

 

P0719 = 1, P0700 = 2

 

 

 

BOP

P0719 = 0, P0700 = 1, P1000 = 1

UP button

DOWN button

or

 

P0719 = 11

 

 

USS on

P0719 = 0, P0700 = 4, P1000 = 1

USS control word

USS control word

or

BOP link

r2032 Bit13

r2032 Bit14

P0719 = 41

USS on

P0719 = 0, P0700 = 5, P1000 = 1

USS control word

USS control word

COM link

or

r2036 Bit13

r2036 Bit14

P0719 = 51

CB

P0719 = 0, P0700 = 6, P1000 = 1

CB control word

CB control word

or

r2090 Bit13

r2090 Bit14

 

P0719 = 61

3.5.5.9Fixed frequency (FF)

P1001 =...

P1002 =...

P1003 =...

P1004 =...

P1005 =...

P1006 =...

P1007 =...

Fixed frequency 1

0.00 Hz

When defining the function of the digital inputs

Can be directly selected via DIN1

(P0701 to P0703), three different types can be

(P0701 = 15 16)

 

selected for fixed frequencies:

 

 

15 = Direct selection (binary-coded)

Fixed frequency 2

5.00 Hz

Can be directly selected via DIN2

In this particular mode, the appropriate

digital input always selects the associated

(P0702 = 15, 16)

 

 

fixed frequency, e.g.:

 

 

Fixed frequency 3

10.00 Hz

Digital input 3 = selects fixed frequency 3.

Can be directly selected via DIN3

If several inputs are simultaneously active,

(P0703 = 15, 16)

 

then these are summed. An ON command is

 

 

additionally required.

Fixed frequency 4

15.00 Hz

16 = Direct selection + ON command

 

 

 

(binary-coded + On / Off1)

Fixed frequency 5

20.00 Hz

In this mode, the fixed frequencies are

 

 

selected as for 15, however these are

Fixed frequency 6

25.00 Hz

combined with an ON command.

 

 

17 = Binary coded selection + ON command

 

 

(BCD-coded + On/ Off1)

Fixed frequency 7

30.00 Hz

The BCD-coded operating mode is effective

 

 

 

for digital inputs 1 to 3.

 

 

 

MICROMASTER 420

Operating Instructions

76

6SE6400-5AA00-0BP0

Page 76
Image 76
Siemens 420 manual Motor potentiometer MOP, Fixed frequency FF