Siemens 420 manual 5.10 JOG, Ramp-function generator HLG

Models: 420

1 190
Download 190 pages 14.8 Kb
Page 77
Image 77

Issue 07/04

3 Functions

P1016 =...

P1017 =...

P1018 =...

Fixed frequency code –

1

1

Direct selection

Bit 0

 

2

Direct selection + ON command

Defines the selection method for fixed

3

Binary coded selection + ON command

frequencies.

 

NOTE

Fixed frequency code –

1

For settings 2 and 3, all parameters P1016 to

Bit 1

 

P1019 must be set to the selected value so that

 

 

the drive inverter accepts the ON command.

Fixed frequency code –

1

 

 

Bit 2

 

 

 

 

 

 

 

3.5.5.10JOG

P1058 =...

P1059 =...

P1060 =...

P1061 =...

JOG frequency right

5.00 Hz

Frequency in Hz when the motor is being jogged in the clockwise direction of rotation.

JOG frequency left

5.00 Hz

Frequency in Hz when the motor is being jogged in the counter-clockwise direction of rotation.

JOG ramp-up time

10.00 s

Ramp-up time in s from 0 to the maximum frequency (P1082). The JOG ramp-up is limited by P1058 or P1059.

JOG ramp-down time

10.00 s

Ramp-down time in s from the maximum frequency (P1082) to 0.

JOG

 

f

 

P1082

 

(fmax)

 

P1058

 

 

t

P1060

P1061

3.5.5.11Ramp-function generator (HLG)

P1091 =...

P1091 =...

P1091 =...

P1091 =...

P1101 =...

P1120 =...

P1121 =...

Skip frequency 1 (entered in Hz)

0.00 Hz

fout

Defines skip frequency 1 which avoids

effects of mechanical resonance and

 

suppresses frequencies within +/- P1101

 

(skip frequency bandwidth).

 

Skip frequency 2

0.00 Hz

 

 

Skip frequency 3

0.00 Hz

 

P1101

 

 

 

 

 

 

Skip frequency

Skip frequency 4

0.00 Hz

 

bandwidth

 

 

P1091

fin

 

 

 

Skip frequency bandwidth

2.00 Hz

Skip frequency

(entered in Hz)

 

 

 

Ramp-up time

10.00 s

f

 

(enters the accelerating time in s)

 

P1082

 

 

 

(fmax)

 

Ramp-down time

10.00 s

f1

 

 

 

(enters the deceleration time in s)

 

 

 

 

 

 

t

 

 

P1120

P1121

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

77