3 Functions

Issue 07/04

IEC Motor

W2 U2 V2

U1 V1 W1

W2 U2 V2

U1 V1 W1

U1

Delta connection

V1

W1

U1

Star connection

V1

W1

e.g.: Volts 230 V (Delta connection) / 400 V (Star connection)

NEMA Motor

 

 

 

 

 

 

 

 

 

T

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connected

 

 

 

 

 

 

Volts

U

V

 

W

Connection

 

 

T4

 

 

together

 

 

 

 

 

 

 

 

 

 

 

 

T7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

low

T1-T7

T2-T8

T3-T9

T4-T5-T6

Y Y

 

 

 

 

 

 

 

 

 

high

T1

T2

 

T3

T1-T7

T2-T8

T3-T9

Y

T T9

 

 

T8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

e.g.: Volts 230 V

YY

(low) /

460 V Y

(high)

6

 

 

T5

 

 

T3

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

Volts

U

V

W

Connected

Connection

 

together

 

 

 

 

 

 

 

low

T1-T6-T7

T2-T4-T8

T3-T5-T9

-

 

∆ ∆

 

high

T1

T2

T3

T4-T7

T5-T8

T6-T9

T3

TT9 TT4

6 7

T8 T5

T2

Fig. 3-18 Motor terminal box

The following must be noted when entering the rating plate data or the ESB data:

The rated motor voltage P0304, the rated motor current P0305 and the stator resistance P0350 must always be entered in accordance with the motor circuit configuration (either delta or star).

If the rated motor data that is available (P0304, P0305, P0350) does not match the motor circuit configuration, then the appropriate conversion (refer to Fig.

3-19) must be made and then entered.

NOTE

The outer conductor voltage/phase-to-phase voltage (voltage U12 between outer conductors L1, L2) and the outer conductor current (phase current) I1 are always specified on the rating plate.

MICROMASTER 420

Operating Instructions

66

6SE6400-5AA00-0BP0

Page 66
Image 66
Siemens 420 manual IEC Motor, Nema Motor