Siemens 420 manual Inverter/motor protection

Models: 420

1 190
Download 190 pages 14.8 Kb
Page 80
Image 80
0
2
100 s

3 Functions

Issue 07/04

3.5.5.14Inverter/motor protection

P0290 =...

P0292 =...

P0335 =...

P0610 =...

P0611 =...

P0614 =...

Inverter overload reaction

0

Selects reaction of inverter to an internal over-temperature.

 

0

Reduce output frequency

 

1

Trip (F0004)

 

2

Reduce pulse frequency and output frequency

 

3

Reduce pulse frequency then trip (F0004)

 

Inverter temperature warning

15 °C

Defines the temperature difference (in ºC) between the Overtemperature trip threshold and the warning threshold of the inverter. The trip threshold is stored internally by the inverter and cannot be changed by the user.

Motor cooling (enters the motor cooling system)

0Self-cooled: Using shaft mounted fan attached to motor

1Force-cooled: Using separately powered cooling fan

Motor I2t reaction

Defines reaction when motor I2t reaches warning threshold.

0Warning, no reaction, no trip

1Warning, Imax reduction, trip F0011

2Warning, no reaction, trip (F0011)

Motor I2t time constant (entered in s)

The time until the thermal limit of a motor is reached, is calculated via the thermal time constant. A higher value increases the time at which the motor thermal limit is reached. The value of P0611 is estimated according to the motor data during quick commissioning or is calculated using P0340 (Calculating of the motor parameters). When the calculation of motor parameters during quick commission is complete the stored value can be replaced by the value given by the motor manufacturer

Motor I2t warning level (entered in %)

100.0 %

Defines the value at which alarm A0511 (motor overtemperature) is generated.

Trip threshold 1.1P0614

P0611

r0027 2

   P0305

r0021

P0310

 

 

Motor

 

 

 

 

 

 

 

 

F0011

 

 

r0034

i2t

 

 

 

 

 

 

 

 

 

temp.

 

 

I_max reduction

 

( i2 t )

 

 

t

reaction

 

 

 

 

 

 

P0610

 

 

A0511

 

 

 

 

 

 

 

 

 

 

 

P0335

P0614

Warning threshold

P0640 =...

Motor overload factor [%]

150.0 %

Defines motor overload current limit in [%] relative to P0305 (rated motor current). Limited to maximum inverter current or to 400 % of rated motor current (P0305), whichever is the lower.

MICROMASTER 420

Operating Instructions

80

6SE6400-5AA00-0BP0

Page 80
Image 80
Siemens 420 manual Inverter/motor protection