Siemens 420 manual Keys and their functions on the operator panel BOP / AOP

Models: 420

1 190
Download 190 pages 14.8 Kb
Page 54
Image 54

3 Functions

Issue 07/04

3.2.3Keys and their functions on the operator panel (BOP / AOP)

Operator

Function

 

Effects

panel/key

 

 

 

 

 

Indicates

The LCD displays the settings currently used by the converter.

 

Status

 

 

 

 

 

 

 

 

 

Pressing the button starts the converter. This button is disabled by default.

 

Start

Activate the button:

 

 

BOP:

P0700 = 1 or P0719 = 10 ... 16

 

 

converter

 

 

AOP:

P0700 = 4 or P0719 = 40 ... 46

on BOP link

 

 

 

 

 

P0700 = 5 or P0719 = 50 ... 56

on COM link

 

 

OFF1

Pressing the button causes the motor to come to a standstill at the

 

 

 

selected ramp down rate.

 

 

Stop

 

Activate the button: see button "Start converter"

 

OFF2

Pressing the button twice (or once long) causes the motor to coast to a

 

converter

 

 

standstill.

 

 

 

 

 

 

 

 

BOP: This function is always enabled

 

 

 

(independent of P0700 or P0719).

 

Change

Press this button to change the direction of rotation of the motor. Reverse is

 

indicated by a minus (-) sign or a flashing decimal point. Disabled by default.

 

direction

 

Activate the button: see button "Start converter".

 

 

 

Jog motor

In the "Ready to power-on" state, when this key is pressed, the motor starts and

 

rotates with the pre-set jog frequency. The motor stops when the button is

 

 

released. Pressing this button when the motor is running has no effect.

 

 

This button can be used to view additional information.

 

 

It works by pressing and holding the button. It shows the following, starting from

 

 

any parameter during operation:

 

 

 

1. DC link voltage (indicated by d – units V).

 

 

2. output current. (A)

 

 

 

3. output frequency (Hz)

 

 

 

4. output voltage (indicated by o – units V).

 

 

5. The value selected in P0005 (If P0005 is set to show any of the above (1 - 4)

 

Functions

then this will not be shown again).

 

 

Additional presses will toggle around the above displays.

 

 

 

 

Jump Function

 

 

 

From any parameter (rxxxx or Pxxxx) a short press of the Fn button will

 

 

immediately jump to r0000, you can then change another parameter, if required.

 

 

Upon returning to r0000, pressing the Fn button will return you to your starting

 

 

point.

 

 

 

 

Acknowledgement

 

 

 

If alarm and fault messages are present, then these can be acknowledged by

 

 

pressing key Fn.

 

 

Access

Pressing this button allows access to the parameters.

 

parameters

 

 

 

 

 

Increase

Pressing this button increases the displayed value.

 

value

 

 

 

 

 

Decrease

Pressing this button decreases the displayed value.

 

value

 

 

 

 

+

AOP menu

Calls the AOP menu prompting (this is only available for AOP).

 

 

 

 

 

Fig. 3-9 Operator panel keys

MICROMASTER 420

Operating Instructions

54

6SE6400-5AA00-0BP0

Page 54
Image 54
Siemens 420 manual Keys and their functions on the operator panel BOP / AOP, Operator Function Effects Panel/key