3 Functions

Issue 07/04

By changing the setting of 50/60 Hz DIP switch, after the drive inverter has been powered-down/powered-up, the parameters for the rated motor frequency P0310, max. frequency P1082 and reference frequency P2000 are automatically pre-set. In addition, the rated motor parameters as well as all of the other parameters which depend on the rated motor parameters, are reset. The units of the power parameters are, depending on P0100, are either interpreted as kW value or hp value.

3.5.2Quick commissioning

If there is still no appropriate parameter set for the drive, then a quick commissioning must be carried-out including a motor data identification routine. The following operator units can be used to carry-out quick commissioning:

BOP (option)

AOP (option)

PC Tools (with commissioning software STARTER, DriveMonitor)

When the quick commissioning is carried-out, the motor – drive inverter is basically commissioned; the following data must be obtained, modified or entered before quick commissioning is started:

Enter the line supply frequency Enter the rating plate data Command / setpoint sources

Min. / max. frequency or ramp-up / ramp-down time Control mode

Motor data identification

Parameterizing the drive with BOP or AOP

The frequency inverter is adapted to the motor using the quick commissioning function and important technological parameters are set. The quick commissioning shouldn't be carried-out if the rated motor data saved in the frequency inverter (4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)- specific) match the rating plate data.

Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities.

START

P0003 = 2

P0010 = 1

 

Factory setting

 

 

 

 

 

User access level *

 

1

 

1Standard: Allows access into most frequently used parameters

2Extended: Allows extended access e.g. to inverter I/O functions

3Expert (For expert use only)

Commissioning parameter *

0

0Ready

1Quick commissioning

30Factory setting

NOTE

P0010 should be set to 1 in order to parameterize the data of the motor rating plate.

MICROMASTER 420

Operating Instructions

62

6SE6400-5AA00-0BP0

Page 62