3 Functions

Issue 07/04

3.11.1PID motorized potentiometer (PID-MOP)

Parameter range:

P2231 – r2250

Warnings

-

Faults

-

Function chart number:

FP3400

The PID controller has a PID motorized potentiometer which can be separately adjusted. The functionality is identical with the motorized potentiometer (refer to Section 3.9), whereby the PID parameters are emulated in the range from P2231 –

r2250 (refer to the comparison Table 3-18).Table 3-18 Correspondence between the parameters

 

PID motorized potentiometer

 

Motorized potentiometer

P2231[3]

Setpoint memory of PID-MOP

P1031[3]

Setpoint memory of the MOP

P2232

Inhibit rev. direct. of PID-MOP

P1032

Inhibit reverse direction of MOP

 

 

 

 

P2235[3]

BI: Enable PID-MOP (UP-cmd)

P1035[3]

BI: Enable MOP (UP-command)

 

 

 

 

P2236[3]

BI: Enable PID-MOP (DOWN-cmd)

P1036[3]

BI: Enable MOP (DOWN-command)

P2240[3]

Setpoint of PID-MOP

P1040[3]

Setpoint of the MOP

 

 

 

 

r2250

CO: Output setpoint of PID-MOP

r1050

CO: Act. output freq. of the MOP

 

 

 

 

MICROMASTER 420

Operating Instructions

108