Page 88
Image 88

3 Functions

Issue 07/04

Parameter P0725 is used to define as to whether digital inputs DIN1 – DIN3 are logical "1" when appropriately connected to 0 V or 24 V. The logical states of the digital inputs can be de-bounced using P0724 and read-out using parameter r0722 (BICO monitoring parameter). Further, this parameter is used to parameterize BICO for the digital inputs (refer to BICO parameterization in the following Section).

P0701 – P0703 (digital inputs 1–3) or P0707 – P0703 (analog input)

The possible settings of the individual inputs are listed in Table 3-10.

Table 3-10 Parameters P0701 – P0706

Parameter value

Significance

0

Digital input disabled

 

 

1

ON / OFF1

 

 

2

ON+reverse / OFF1

3

OFF2 – coast to standstill

 

 

4

OFF3 – quick ramp-down

 

 

9

Fault acknowledge

 

 

10

JOG right

11

JOG left

 

 

12

Reverse

 

 

13

MOP up (increase frequency)

14

MOP down (decrease frequency)

15

Fixed setpoint (direct selection)

 

 

16

Fixed setpoint (direct selection + ON)

 

 

17

Fixed setpoint (binary-coded selection + ON)

25

Enable DC braking

 

 

29

External trip

 

 

33

Disable additional frequency setpoint

 

 

99

Enable BICO parameterization

Example:

An ON/OFF1 command should be realized using digital input DIN1.

P0700 = 2 Control enabled via terminal strip (digital inputs)

P0701 = 1 ON/OFF1 via digital input 1 (DIN1)

MICROMASTER 420

Operating Instructions

88

6SE6400-5AA00-0BP0