Issue 07/04

3 Functions

Example:

The permanent PID controller should fulfill the following

 

secondary conditions/limitations:

 

 

 

PID controller enable and PID setpoint input via PID fixed

 

frequencies and PID actual value via the analog input.

 

 

Parameterizations:

 

 

 

a. Permanent PID controller enable:

P2200

= 1.0

 

b. Setpoint input via PID-FF:

P2253

= 2224

 

c. Actual value input via analog input ADC:

P2264

= 755

The supplementary (additional) setpoint is added to the main setpoint (PID-SUM) and the sum is fed to the setpoint filter (PID-PT1) at the setpoint-actual value summation point via the PID ramp-function generator (PID-RFG). The source of the supplementary setpoint (BICO parameter P2254), the ramp-up / ramp-down times of the PID ramp-function generator (P2257, P2258) as well as also the filter time (P2261) can be adapted to the particular application by appropriately parameterizing the corresponding parameters.

Similar to the PID setpoint branch, the actual value branch of the technological controller has a filter (PID-PT1) which can be set using parameter P2265. In addition to the smoothing, the actual value can be modified using a scaling unit (PID-SCL).

The technological controller can be parameterized as either P, I or PI controller using parameters P2280 and P2285.

 

 

 

 

 

P2293

 

 

 

 

 

 

P2291

 

 

 

 

 

 

 

P2280 P2285

 

 

 

 

 

 

Kp

Tn

y

 

PID

 

 

 

+

 

x

Motor

setpoint

 

 

 

-

 

 

control

 

 

 

 

 

 

 

 

 

r2262

 

r2273

 

 

r2294

 

P2267

y

 

P2292

 

 

 

PID

 

 

 

 

 

 

 

 

x

r2272

 

 

 

feedback

 

 

 

 

 

 

P2268

 

 

 

P2293

 

 

Fig. 3-37

PID controller

 

 

 

 

 

 

For specific applications, the PID output quantity can be limited to defined values. This can be achieved using the fixed limits - P2291 and P2292. In order to prevent the PID controller output exercising large steps at power-on, these PID output limits are ramped-up with ramp time P2293 from 0 to the corresponding value P2291 (upper limit for the PID output) and P2292 (lower limit for the PID output). As soon as these limits have been reached, the dynamic response of the PID controller is no longer limited by this ramp-up/ramp-down time (P2293).

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

107

Page 107
Image 107
Siemens 420 manual Parameterizations