Siemens 420 manual USS at the COM link RS485

Models: 420

1 190
Download 190 pages 14.8 Kb
Page 97
Image 97

Issue 07/04

3 Functions

NOTE

A communications (CB) module as well as a programming / operator unit can be simultaneously connected to the COM link interface via terminals 14/15 (USS). This is the reason that the communications module has priority over USS. In this case, the USS node (USS station) via the COM link is de-activated.

USS at the COM link (RS485)

Contrary to PROFIBUS, the RS485 port (terminals 14/15) is not optically isolated (not floating). When installing the system, it must be ensured that EMC faults do not result in communication failures or damage to the RS485 drivers.

The following measures should be taken as a minimum:

1)Expose the motor shield and correctly connect the shield at both ends of the cable. If at all possible, avoid interrupting the cable. However, if this cannot be avoided, then it is crucial that the shield at the connection locations is continued in compliance with EMC rules.

2)All node points should be well-grounded (EMC ground).

3)Interference suppression elements should be connected to all relay coils.

4)The cables, as far as possible, should be routed separately from other cables. Especially RS485 cables should be kept away from motor cables.

5)The shields of RS485 cables must be correctly grounded.

If the AOP communicates using the USS protocol, then contrary to the BOP, the appropriate USS parameters must be set (Table 3-12 and Table 3-13).

In order to ensure error-free communications, the appropriate communication parameters must be set and harmonized with one another – both in the drive converter as well as in the connected drive unit or in the connected option module. In this case, the relevant operating instructions should be used for the AOP and for the communication modules.

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

97

Page 97
Image 97
Siemens 420 manual USS at the COM link RS485