3 Functions

Issue 07/04

The fixed frequencies can be selected via the digital inputs as well as also via serial communication interfaces. The fixed frequency is selected, when using digital inputs, using 2 techniques. This will be shown in the following example using the fixed frequency P1001 and digital input 1 (refer to Fig. 3-32).

a)

Standard methods

P0701

= 15

b)

BICO methods

P0701

= 99, P1020 = 722.0, P1016 = 1

P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1

 

 

P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1

 

 

 

 

P1016

 

 

 

P1020

1

 

 

DIN1

r0722.0

 

 

 

0

2,3

 

 

 

 

 

 

 

 

P1017

0

 

 

 

 

 

 

P1021

P1001

 

DIN2

r0722.1

1

 

 

 

 

 

 

0

2,3

 

+

 

 

 

 

r1024

 

.

 

0

+

 

. .

 

 

 

P1002

.

 

.

 

 

 

 

 

 

 

 

. .

Fig. 3-32 Example for directly selecting FF1 via DIN1 and FF2 via DIN2

Direct selection + ON command

When this fixed frequency is selected, the fixed frequencies are also directly selected whereby the selection is combined with the ON command. When this technique is used, a separate ON command is not required. The following is obtained essentially analog to the example shown above:

a)

Standard method

P0701

= 16

b)

BICO method

P0701

= 99, P1020 = 722.0, P1016 = 2

MICROMASTER 420

Operating Instructions

100

6SE6400-5AA00-0BP0

Page 100
Image 100
Siemens 420 manual Direct selection + on command