3 Functions

Motor data identification routine

START

Factory setting: Bold

Ambient Motor temp.

5 °C

?

yesno

Allow the motor

to cool down

Ambient motor temperature (entered in °C)

The motor ambient temperature is entered at the instant that motor data is being determined (factory setting: 20 °C).

The difference between the motor temperature and the motor ambient temperature must lie in the tolerance range of approx. ± 5 °C. If this is not the case, then the motor data identification routine can only be carried-out after the motor has cooled down.

P1910 = 1

ON

A0541

Select motor data identification

0Disabled

1Identification of all parameters with parameter change

NOTE:

For P1910 = 1 P0340 is internally set to P0340 = 1 and the appropriate data calculated (refer to parameter list P0340)

Power-up the motor

The ON command initiates the measuring operation. In so doing the motor aligns itself and conducts current. Alarm message A0541 (motor data identification routine active) is output.

After the motor data identification routine has been completed:

1.P1910 is reset (P1910 = 0)

2.A0541 is withdrawn

MICROMASTER 420

Operating Instructions

6SE6400-5AA00-0BP0

71