3 Functions

Issue 07/04

Table 3-19 BICO parameters for ramp-function generator

 

Parameter

Description

P1140

BI: RFG enable

The ramp-function generator output is set to 0 if the

 

 

binary signal = 0.

P1141

BI: RFG start

The ramp-function generator output keeps its actual

 

 

value if the binary signal = 0.

P1142

BI: RFG enable setpoint

If the binary signal = 0, then the ramp-function

 

 

generator input is set to 0 and the output is reduced

 

 

to 0 via the ramp-function generator ramp.

The ramp-function generator itself is enabled after the pulses have been enabled (inverter enable) and after the excitation time has expired (P0346). After limiting to the maximum speeds for the positive and negative directions of rotation (P1082, -P1082 or 0 Hz for the direction of rotation inhibit) the setpoint speed for the control is obtained (r1170).

NOTE

The maximum drive inverter frequency is defined in the setpoint channel using parameter P1080. The maximum possible frequency is 650 Hz.

MICROMASTER 420

Operating Instructions

114

6SE6400-5AA00-0BP0