Carrier Access Access Navigator user manual CLI Minor Alarm Message and Trouble Clearing Procedure

Models: Access Navigator

1 704
Download 704 pages 57.28 Kb
Page 325
Image 325

Alarm Clearing

Clear Alarms – FDL

Table 14-3 CLI Minor Alarm Message and Trouble Clearing Procedure

Event Message

Description

Trouble Clearing Procedure

-48V DC power A/B

-48V DC power supply to the

Check power cable connection or

Low or Missing

controller (A or B) is low or

battery voltage of the reporting

 

missing. Under normal condition

controller card.

 

power is shared between controller

 

 

cards.

 

 

 

 

Alarm Input 1/2/3

Contact closure was detected on

The alarm is cleared when the

Detected

the indicated alarm input (1,2, or

contact is opened.

 

3). Alarm inputs can be wired to

 

 

the facility alarm system. Under

 

 

normal conditions the facility

 

 

alarm system should provide open

 

 

contacts to the alarm inputs.

 

 

Providing contact closure to an

 

 

alarm input results in this alarm.

 

 

 

 

Controller A/B

Controllers do not support the

Remove the standby controller and

Incompatible

same functionality; for example,

replace with a compatible

 

one supports EOC/TMC and the

controller (see Replace Controller

 

other does not.

Card on page 16-3or update

 

 

controller with compatible

 

 

software (see Update Controller

 

 

Card Software on page 17-1).

 

 

 

Controller A/B Removed

Upon removal the controller card

Insert a good controller card into

 

(A or B), the remaining controller

the empty slot

 

card is now active.

 

 

 

 

Controller A/B software

Controller card software versions

Update offending controller with

version mismatch

do not match.

appropriate software (see Update

 

 

Controller Card Software on

 

 

page 17-1).

 

 

 

DS1 n Major Line CV

DS1 is receiving Line Code

Correct the problem with the

 

Violations at a rate greater than

incoming DS1 signal, or use

 

1.0 x 10-3. This indicates a weak

following command to provision

 

signal or faulty wiring.

the DS1 as out of service:

 

 

set ds1 <n> <updown>

 

 

 

Access Navigator - Release 1.8

August 2003

14-5

Page 325
Image 325
Carrier Access Access Navigator user manual CLI Minor Alarm Message and Trouble Clearing Procedure, Card Software on