Alarm Clearing

Clear Alarms – EOC

Table 14-5. EOC Major Alarm Message and Trouble Clearing Procedure

Event Message

Description

Trouble Clearing Procedure

System Alarm State

Event Report Service Problem

The alarm is cleared after all

Change

(5ESS only).

events reportable to the switch

 

The severity of the system alarm

have been cleared.

 

state has changed. Only those

 

 

events reportable to the switch and

 

 

excluding Service Problems are

 

 

included in the system alarm state.

 

 

 

 

Table 14-6 EOC Minor Alarm Message and Trouble Clearing Procedure

Event Message

Description

Trouble Clearing Procedure

-48V DC power A/B

Event Report Power Problem.

Check power cable connection or

Low or Missing

-48V DC power supply to the

battery voltage of the reporting

 

controller (A or B) is low or

controller card.

 

missing. Under normal condition

 

 

power is shared between controller

 

 

cards.

 

 

 

 

Alarm Count List

Event Report Service Problem.

The alarm is cleared after all

Change

(Reported only if the alarm count

events reportable to the switch

 

list has been created. The alarm

have been cleared

 

count list is created by DMS

 

 

switches.)

 

 

The number of alarms active in the

 

 

Access Navigator has changed.

 

 

Only those alarms reportable to

 

 

the switch and excluding Service

 

 

Problems are included in the alarm

 

 

count list.

 

 

 

 

Alarm Input 1/2/3

Event Report Environmental

The alarm is cleared when the

Detected

Problem. Contact closure was

contact is opened.

 

detected on the indicated alarm

 

 

input (1,2, or 3). Alarm inputs can

 

 

be wired to the facility alarm

 

 

system. Under normal conditions

 

 

the facility alarm system should

 

 

provide open contacts to the alarm

 

 

inputs. Providing contact closure

 

 

to an alarm input results in this

 

 

alarm.

 

 

 

 

14-10