Carrier Access Access Navigator user manual DC Power Connections, Installation Summary

Models: Access Navigator

1 704
Download 704 pages 57.28 Kb
Page 139
Image 139

Electrical Installation

DC Power Connections

DC Power Connections

Installation Summary

￿Precautions ... 6-35

￿Tools and Materials ... 6-35

￿Wire Power Connectors ... 6-36

￿Verify Wiring ... 6-37

￿Connect Power Plugs to Access Navigator ... 6-37

Precautions

DANGER! HIGH VOLTAGE SHOCK HAZARD. DO NOT WIRE CONNECTORS WHILE POWER IS ON.

CAUTION! BOTH POWER CONNECTORS MUST BE WIRED AND CONNECTED TO POWER SOURCES. FAILURE TO DO SO WILL DISABLE REDUNDANT SWITCHING FEATURES AND MAY INTERRUPT SERVICE.

WARNING! POWER INPUT CONNECTORS ARE FOR –48V DC POWER ONLY.

Tools and Materials

NOTE: If the power connector is wired to a fuse panel, use a 5.0 Amp slow-blow fuse.

Obtain the following tools and materials:

Pliers, needle nose

Cutters, diagonal

Wire stripper, 16-26 AWG

Continuity tester

Volt-ohm meter

16 or 18 AWG insulated copper wire for power connections, as required by standard wiring practices

Access Navigator - Release 1.8

August 2003

6-35

Page 139
Image 139
Carrier Access Access Navigator user manual DC Power Connections, Installation Summary