Carrier Access Access Navigator user manual Electrical Installation

Models: Access Navigator

1 704
Download 704 pages 57.28 Kb
Page 150
Image 150

Electrical Installation

Verify Alarm Output Connections

2.Verify major output alarm functions as follows.

Enter the following command to simulate major alarm. set alarms major on

Requirement: Major alarm relay output contacts close (see Figure 6-16 on page 6-29).

Requirement: Active Controller card Major Alarm indicator lights (Figure 6-30).

Enter the following command to turn off major alarm. set alarms major off

Requirement: Major alarm relay output contacts open.

Requirement: Active Controller card Major Alarm indicator goes off.

3.Verify minor output alarm functions as follows.

Enter the following command to simulate minor alarm. set alarms minor on

Requirement: Minor alarm relay output contacts close (see Figure 6-16 on page 6-29).

Requirement: Active Controller card Minor Alarm indicator lights (Figure 6-30).

Enter the following command to turn off minor alarm. set alarms minor off

Requirement: Minor alarm relay output contacts open.

Requirement: Active Controller card Minor Alarm indicator goes off.