Electrical Installation

Verify Alarm Output Connections

2.Verify major output alarm functions as follows.

Enter the following command to simulate major alarm. set alarms major on

Requirement: Major alarm relay output contacts close (see Figure 6-16 on page 6-29).

Requirement: Active Controller card Major Alarm indicator lights (Figure 6-30).

Enter the following command to turn off major alarm. set alarms major off

Requirement: Major alarm relay output contacts open.

Requirement: Active Controller card Major Alarm indicator goes off.

3.Verify minor output alarm functions as follows.

Enter the following command to simulate minor alarm. set alarms minor on

Requirement: Minor alarm relay output contacts close (see Figure 6-16 on page 6-29).

Requirement: Active Controller card Minor Alarm indicator lights (Figure 6-30).

Enter the following command to turn off minor alarm. set alarms minor off

Requirement: Minor alarm relay output contacts open.

Requirement: Active Controller card Minor Alarm indicator goes off.