HP recommends the HP
Figure 21: MCS 5042 Water
Item | Description (Quantity) |
|
|
1 | Main hose assembly* (2) |
|
|
2 | |
|
|
3 | Viton gasket (2) |
|
|
4 | M6 screw (4) |
|
|
5 | 5mm Hex |
|
|
6 | Warning label (2) |
|
|
7 | M5.5 x 10 self tapping screw |
| (8) |
|
|
8 | Hose mounting brackets with |
| hose clamps (2) |
|
|
9 | Top cover plate (1) |
|
|
10 | Rear cover plate (1) |
|
|
*Not drawn to scale. The actual length of the main hose is approximately 3.5 m (11.5 ft).
Caution:
You must properly connect the cabinet and facility cool water inlet and warm water outlet hoses. The MCS 5042 does include a check valve to prevent the reverse flow of coolant.
The MCS 5042 has the connecting fittings inside the unit, approximately 600 mm (24 inches) above the floor on the rear side. It allows the main coolant hoses to be routed either down through the cutouts in a raised floor (HP recommended) or up through openings in the top of the cabinet and above the unit or through the back of the cabinet and above the floor as shown in Figure 22. The left (blue) hose designates the chilled water supplied to the MCS 5042 and the right (red) hose is the warm water exiting from the MCS 5042.
31