The wider opening in the back of the IT rack is optional.

Figure 26: Recommended floor cutouts (single rack configuration)—Option 1 (MCS 5042 cooling unit side flush to tile)

Note:

The wider opening in the back of the IT rack is optional.

Note:

The floor tile sizes used in Figure 26 are 600 mm x 600 mm (23.6 inches x 23.6 inches). Floor tile sizes vary.

Note:

The allowable tolerances are +/- 3.2 mm (+/- 0.125 inches). When installing multiple MCS 5042 units in a row, you must consider the tolerances as you plan the cutouts.