HP Modular Cooling System manual The wider opening in the back of the IT rack is optional

Models: Modular Cooling System

1 60
Download 60 pages 37.09 Kb
Page 38
Image 38
Manual background

Figure 27: Recommended floor cutouts (single rack configuration)—Option 2 (MCS 5042 rack side flush to tile)

Note:

The wider opening in the back of the IT rack is optional.

Note:

The floor tile sizes used in Figure 27 are 600 mm x 600 mm (23.6 inches x 23.6 inches). Floor tile sizes vary.

Note:

The allowable tolerances are +/- 3.2 mm (+/- 0.125 inches). When installing multiple MCS 5042 units in a row, you must consider the tolerances as you plan the cutouts.

38

Page 38
Image 38
HP Modular Cooling System manual The wider opening in the back of the IT rack is optional