Cooling considerations

24Can the room temperature be maintained between the recommended 18°C (64.4 °F) Min. –27°C (80.6 °F) Max. and allowable 15°C (59 °F) Min. –32°C (90 °F) Max. (up to 5000 ft) Derate 1°C/1000 ft

above 5000 ft and up to 10,000 ft

25Can humidity level be maintained at the recommended level of

5.5°C (41.9°F) dew point to 60% relative humidity and 15°C (59°F) dew point, with an allowable humidity levels of 20% to 80%

26Are air-conditioning filters installed/clean?

Water preparation considerations

27Has the water been tested for acceptable quality for use in the MCS 5042?

28If the water quality is unacceptable, have adequate treatment and filtration measures been put into place?

29Have the water temperature and flow been evaluated?

30If temperature and flow are not adequate, have supplemental chiller units and water pumps been implemented to achieve ample performance?

31Has an adequately sized water-to-water heat exchanger been implemented to provide a dedicated water loop to the MCS 5042?

32Has piping of an appropriate diameter, material, and pressure tolerance been installed to reach the back of each MCS 5042?

33Is there a provision for fluid collected from the condensation and overflow hoses at each MCS 5042?