MCS 5042 specifications
Physical specifications
Table 1: MCS 5042 physical specifications of a standard single rack and server cabinet configuration
| Packaged system | Unpackaged system | Unpackaged |
Parameter | (as shipped on pallet) | (off pallet, unwrapped) | CTO system |
|
|
|
|
Height | 2285 mm (90 in) | 2007 mm (79 in) | 2007 mm (79 in) |
|
|
|
|
Width | 1219 mm (48 in) | 904 mm (35.6 in) | 904 mm (35.6 in) |
|
|
|
|
Depth | 1829 mm (72 in) | 1510 mm (59.5 in) | 1510 mm (59.5 in) |
|
|
|
|
Weight | 732 kg (1614 lb) 1 | 478 kg (1054 lb) 2 | 1521 kg (3353 lb) 3 |
1Weight for a completely packaged system with unpopulated server rack
2Weight for an unpackaged system with unpopulated server rack
3Approximate weight for an unpackaged CTO system (Actual weight varies, according to configuration.)
Note:
If the top shipping bracket interferes with deploying the MCS 5042, you can remove it. With the top shipping bracket, the total height of the unpackaged system is 2069 mm (81.5 inches).
Electrical specifications
Table 2: MCS 5042 electrical specifications
Parameter | Value | Comments |
|
|
|
Operating voltage | 208/230 VAC +/- 10%, 50/60 Hz |
|
|
|
|
AC line phase | Single |
|
|
|
|
Maximum input current | 18 A | Per line cord |
|
|
|
Maximum inrush current | 200 A | Per line cord |
|
|
|
20 ms |
| |
|
|
|
Transfer time of AC transfer switch | 2 s |
|
|
|
|
Circuit breaker rating | LAHJ | Per cord |
|
|
|
Power factor | > 0.95 | At all loads |
|
|
|
Ground leakage current | < 19.4 mA | Per line cord |
|
|
|
Rated power consumption | 2800W | Steady state |
|
|
|
Power cords | 208 V, 20 A | NEMA |
(included with the MCS 5042) |
| 700105 (Qty 2) |
|
| |
| 250 V, 16 A | IEC |
|
| (Qty 2) |
|
|
|
9