HP Modular Cooling System manual

Models: Modular Cooling System

1 60
Download 60 pages 37.09 Kb
Page 46
Image 46
After calculating the total expected required heat load, use the charts in “Determining heat load capacities” to determine required water flow and pressure based on potential chilled water temperatures. The pressure (PSID) must be measured prior to the cold water inlet/after warm water outlet. All water system equipment, materials, and installation must comply with any applicable construction codes and LAHJ.

Table 9: Rack Cooling Loop Sizing Chart

Installed

Quantity

Max. Watts

Max. CFM

Max. Watts

Max. CFM

Component

Generated

Required

Total

Total

 

Component 1:

Component 2:

Component 3:

Component 4:

Component 5:

Component 6:

Component 7:

Component 8:

Component 9:

Component 10:

Total for Cabinet 1

1An approximate value can be estimated by assuming all power entering the cabinet is converted to heat.

After calculating the total expected required heat load, use the charts in “Determining heat load capacities” to determine required water flow and pressure based on potential chilled water temperatures. The pressure (PSID) must be measured prior to the cold water inlet/after warm water outlet. All water system equipment, materials, and installation must comply with any applicable construction codes and LAHJ.

46

Page 46
Image 46
HP Modular Cooling System manual