Solution:

1.View the Overview menu to distinguish which temperature sensor is different from the other temperature sensors.

2.After discovering which temperature sensor is not working properly, remove that module and reinstall it. If the difference is in the Server Exhaust Temperature, replace the appropriate fan unit. If the difference is in the Server Intake Temperature, replace the appropriate HEX unit.

If the warning message does not clear after the module is reseated, replace the HEX unit with a CSR part. For more information on CSR parts, see "Replaceable parts and maintenance and service information (on page 63)."

Low water flow

Indicators

Meaning

 

 

Actual operator display alarm

Water flow Low

message

 

 

 

Actual web interface alarm

Water flow Low

message

 

 

 

Condition

No or low water flow

 

 

Modules

Water group

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

Verify the water supply.

Water temperature input is out of range

Indicators

Meaning

 

 

Actual operator display alarm

Water Temp. In Failed

message

 

 

 

Actual web interface alarm

Water Unit Temperature Input Out of Range

message

 

 

 

Condition

Water temperature sensor is not working properly (possible open circuit)

 

 

Sensors

Water group sensor

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

1.Verify the water supply.

2.Verify whether the water temperature is below or above the water temperature expected range.

3.Contact your building supervisor.

4.Contact HP, or see the HP website (http://www.hp.com).

Water temperature output is out of range

Operator display 48