1.Verify the water valve is closed.

2.Contact HP, or see the HP website (http://www.hp.com).

Leak detector sensor is not working properly

Indicators

Meaning

 

 

Actual operator display alarm

Leak detector?

message

 

 

 

Actual web interface alarm

Leak detector Failed

message

 

 

 

Condition

Leak detector sensor is not working properly

 

 

Sensors

Leak detector sensor

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

Contact HP, or see the HP website (http://www.hp.com).

Uneven heat load

Indicators

Meaning

 

 

Actual operator display alarm

Heat Load?

message

 

 

 

Actual web interface alarm

Heat Load Warning

message

 

 

 

Condition

Measured air temperature values dramatically different from top to bottom

 

 

Sensors

Air temperature sensors

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

1.Verify that nothing is blocking the heat path.

2.Verify that the server is loading.

3.Adjust the Temperature Difference for Heat Load Warning in the Advanced tab.

Heat overload condition (High Temperature Threshold field)

Indicators

Meaning

 

 

 

 

Actual operator display alarm

Temperature Warning

 

message

 

 

 

 

 

Actual web interface alarm

Temperature Warning

 

message

 

 

 

 

 

Condition

Heat overload condition

 

 

 

 

Modules or sensors

Average server air temperature is above the temperature assigned in the

 

 

web interface Intake Temp tab High Temperature Threshold field

 

 

 

 

SNMP notification

Critical

 

 

 

 

Type of message

Alarm

 

 

 

 

 

Operator display 50