•Warning Temperature Threshold—Temperature difference above Server Intake Temperature Set Point for temperature warning message
•Low Temperature Threshold—Temperature difference below Server Intake Temperature Set Point for temperature warning message
The following values are displayed in the web interface for information only:
•Fan Speed Target—Displays the percentage of the fan maximum speed
•Water Valve—Displays the water valve state
•Cooling Module 1 through 3—Displays the Server Intake and Server Exhaust Temperature and the RPM of each cooling unit
•Water Inlet Temperature—Displays the temperature of the water coming into the MCS unit to be used to cool the servers
•Water Outlet Temperature—Displays the temperature of the water after removing the server heat
•Water Flow—Displays the value of the water flow in liters/gallons per minute
Management module componentsThe management module is located on the inside of the MCS front door.
Item | Reference | Description |
| | |
1 | C key | Used to confirm warnings, critical alarms, and |
| | configuration setting changes, as well as to turn off the |
| | audible alarm. Press and hold the C key for five |
| | seconds, or click the Clear Alarms button on the Web |
| | interface Setup tab>General menu, to confirm these |
| | situations. |
| | |
Management module 31