b.Click Scan for hardware changes to refresh the screen and display the changes.

Connecting the USB communications port

NOTE: This port is only used for firmware upgrades. For additional information, see "Updating the UPS firmware (on page 43)."

Connecting the REPO port

WARNING: The pins on the REPO port are polarity sensitive. Be sure to verify polarity while connecting the REPO port.

WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a UPS installed in a computer equipment room must be connected to a REPO circuit.

IMPORTANT: The remote switch must be in the Off (open) position to enable power to the output receptacles.

Installation and configuration 21

Page 21
Image 21
HP R7000 manual Installation and configuration