Specifications

UPS physical specifications

Parameter

Value

 

 

Height

17.1 cm (6.75 in)

Depth

73.4 cm (28.9 in)

Width

43.7 cm (17.2 in)

Weight

75 kg (165 lb)

Ambient operation

0~40°C

ERM physical specifications

Parameter

Value

 

 

Height

12.7 cm (5 in)

Depth

71.9 cm (28.3 in)

Width

43.8 cm (17.24 in)

Weight

63 kg (139 lb)

UPS input specifications

NOTE: An asterisk (*) indicates the default setting.

UPS model

Utility voltage

Available settings

Dedicated

Line cord

 

 

frequency (Hz)

utility voltage (VAC)

branch circuit

 

 

 

 

 

rating (A)

 

 

 

 

 

 

 

R7000

NA/JPN

50/60

200/208*/220/230/

40

Nondetachable power

 

 

 

240

50 low input

cord with NEMA

 

 

 

 

 

CS8265C plug

 

 

 

 

 

 

R7000

INTL

50/60

200/208/220/230*/

32

Nondetachable power

 

 

 

240

 

cord with 32 A IEC-309

 

 

 

 

 

plug

 

 

 

 

 

 

UPS output specifications

UPS model

Load

Circuit

Output receptacles

Maximum current

 

segment

breaker

 

 

 

 

 

 

 

 

 

R7000 NA/JPN

1

20 A¹

2 x IEC-320-C19

16

A per receptacle²

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

Specifications 50