UPS model

Load

Circuit

Output receptacles

Maximum current

 

segment

breaker

 

 

 

 

 

 

 

 

 

 

 

1 x L6-30R

Up to full UPS power rating

 

 

 

 

 

 

 

2

20 A¹

2 x IEC-320-C19

16

A per receptacle²

 

 

 

 

 

 

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

R7000 INTL

1

20 A¹

2 x IEC-320-C19

16

A per receptacle²

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

 

 

1 x IEC-309-32A

Up to full UPS power rating

 

 

 

 

 

 

 

2

20 A¹

2 x IEC-320-C19

16

A per receptacle²

 

 

 

 

 

 

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

1The circuit breakers protect the C19 and C13 outlets.

2If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension bar is 10 A. The total maximum current for the extension bar is 12 A.

Power protection specifications

UPS model

VA

Nominal power

Nominal voltage

 

 

 

rating (W)

setting

 

 

 

 

 

R7000

NA/JPN

7200

7200

200/208, 220,

 

 

 

 

230,

240

 

 

 

 

 

 

R7000

INTL

6500

6500

220,

230, 240

Voltage specifications

Configuration setting (VAC)

Available nominal output voltage

 

(VAC)

 

 

200/208

204

220

220

230

230

240

240

Output tolerance specifications

Source of power

Regulation

 

 

Utility power (nominal

-10% to +6% of nominal output voltage rating

range)

(within the guidelines of the Computer Business

 

Equipment Manufacturers Association)

Battery power

±5% of nominal output voltage rating

Output feature specifications

Feature

Specification

 

 

Online efficiency

94% nominal input voltage

Specifications 51

Page 51
Image 51
HP R7000 manual Power protection specifications, Voltage specifications, Output tolerance specifications