HRView Function Manual | 3. Controller Parameter Setup |
(2)To use
Condition setup and controller parameter should be the same as follows. The Baudrate of the Serial Port 2 should have the same setup as BD473 setup. However, the rest of the communication options should be the same as follows.
When both 『27: Serial Port 1』 and 『33: Serial Port 2』 are set as “FileMng,” Serial Port 1 has a priority, and HRView communication can be done only with Serial Port 1.
The Baudrate of the Serial Port 1 should have the same setup as HRView setup. However, the rest of the communication options should be the same as follows.
Constant Setup Group (1) → 『13: Serial Port』 → 『3: Serial Port 1』
08:09:05 *** Serial Port 1 *** A:0 S:4
Baudrate = <38400,19200,9600,4800,2400>
Character length | = <7,8> bit |
Stop bit | = <1,2> bit |
Parity bit | = <Disable,Odd,Even> |
Echo | = <Disable,Enable> |
Press [Enable]+[Arrow].
>_
Save
Condition Set → 『27: Serial Prot #1』: Set as FileMng
08:09:05 *** Condition Set *** A:0 S:4
1:Mode =<1Step,1Cycle,Continuous>
2:Start=<Internal,External,Remote>
3:External program =<Disable,Enable>
4:Robot lock =<Disable,Enable>
5:Conveyor Oper=<Normal,Simulat.,Test>
7:Search range =[0.0]
8:Search reference Pt. record=<Off,On>
9: Speed rate=[100] | Gun =<DSBL,ENBL> |
13:Rec speed type=<Standard,[%],[mm/s]>
23:Step go/back max.speed = [250]mm/s
27:Serial port #1 =<FileMng,Sens>
Press [Enable]+[Arrow]. |
| |
>_ |
|
|
Service | Previous Next | Done |