| Introduction 1 | |
| Digital inputs |
|
Read | Read the on or off of all inputs | |
Pulse widths | The duration of a single or total on/off time of consecutive | |
| pulses can be resolved to the nearest 0.00 seconds for a max | |
| total of 10.9 minutes, or 46.6 hours with multiplied resolution. | |
| Positive or negative edges initiate measurements. The time | |
| scale can be multiplied by a factor of | |
| basis. | |
Pulse counting | Pulses can be counted up to a total or 65,535. To be reliably | |
| counted, pulses must have minimum on and off times of 1 | |
| mSec. Thus the maximum counting rate for a 50% duty cycle | |
| squarewave with equal on and off times for a total of 2 mSec. | |
| Would be 500Hz. | |
Edge detection | Off to on and on to off transitions can be detected within 1 | |
| mSec. Of their occurrence. Action is only reported every | |
| 10mSec. |
Note: The response time performance of digital input instructions can be limited by the delay in the input modules themselves which can nave on plus off delays of up to 40 mSec.
| Digital outputs |
Set Outputs | Can set individual or multiple outputs on or off Modifiers |
One Shot | Can generate on or off pulse durations of up to 655.35 seconds |
| with a resolution of 0.01 seconds. Resolution can be further |
| multiplied by a factor of |
Delayed | Can generate on or off pulse durations of up to 655.35 seconds |
| with a resolution of 0.01 seconds. Resolution can be further |
| multiplied by a factor of |