The Basic I/O 1

DIGITAL INPUTS:

Digital input modules detect the presence or absence of a field signal. Module types vary from AC to dry contact sense. Because the industry standard modules are optically isolated, the response time performance of digital input instructions can be limited by the delay in the input modules themselves. Some modules can have rise and fall times of up to 40 milliseconds.

Digital input instruction types are:

 

Read

Read the On or Off state of all inputs. This data is

 

updated every 10 Milliseconds.

Edge Detection

Off-to- On and On-to-Off transitions can be detected

 

within 1 millisecond of their occurrence. Action is

 

only reported every 10 milliseconds.

Pulse Widths

BASIC I/Os can report pulse width measurements

 

from .01 seconds to 46.6 hours. Minimum resolution

 

is .01 seconds (Pulse widths up to 10.9 minutes).

 

Either on or off pulses can be measured.

Pulse Counting

Pulses can be counted up to a total of 65,535. To be

 

reliably counted, pulses must have a minimum On and

 

Off time of 1 millisecond. Thus the maximum

 

counting rate for a 50% duty cycle square wave is

 

once every 2 milliseconds (500Hz).

Frequency

Direct frequency measurements can be made on

 

digital inputs at rates of up to 500 Hz with a user

 

specified time base of from .01 to 2.55 seconds.

1-4(Vol.1)