Setup & Installation 2

RS-485 Programming:

The BASIC I/O will work equally well when connected to either RS-422 or RS-485. However special host programming considerations may be necessary when implementing an RS-485 network. Unlike RS-422 where both the transmit and Receive signals have their own differential pair of conductors, RS-485 utilizes only one differential pair. The single pair of conductors is used bidirectionally and handles both transmit and receive signals. In order for this to be possible, the transmitter for each device on this type of network must be enabled and disabled whenever a message is to be sent. The transmitter for the BASIC I/O is designed to handle this control automatically. However, the transmitter control for most popular RS-485 cards that are installed in the Host computer must be controlled by the user program. This control is not straight forward and may impact the overall system throughput with inherent delay periods. The following is a typical instruction/ response transaction between a host computer and a BASIC I/O using RS-485.

1)The Host computer enables its RS-485 transmitter (usually via the RTS line)

2)The Host then sends an instruction to the BASIC I/O in the form of an ASCII printable string.

3)Once the Host determines that the string has been completely sent, the RS-485 transmitter is disabled.

4)Every BASIC I/O on the network receives the instruction and begin to decode it. That particular BASIC I/O addressed begins to construct a response.

5)Once the carriage return is of the instruction is received, the BASIC I/O begins to transmit a response.

6)The Host receives the response and takes the appropriate action.

This interaction is heavily dependant on asynchronous timing. Usually, the Host software has no real means of determining that the instruction has been completely sent. This means that the program must calculate the

2-6(Vol.1)

Page 23
Image 23
I-O Display Systems Basic I/O Product manual RS-485 Programming