SP Switch environment (MAP 0600)
3.Is the measured resistance now within the acceptable range? v If yes, go to ªStep
vIf no, go to ªStep
Step
You replaced the inner chassis cable and the front chassis cable but the measured resistance is still outside of the acceptable range.
1.This indicates that there is still a problem.
2.Replace the switch supervisor card.
3.Go to ªStep
Step
You have voltage shutdown condition, the supervisor control cable appears to be okay, and the resistance value you measured in Table
1.Reconnect cable
2.Repeat resistance measurement from ªStep
3.Is the measured resistance within the acceptable range?
v If yes, replace switch power supply 1 and the switch supervisor card.
a. Go to ªStep
Step
With cable
1.Reconnect cable
2.Repeat resistance measurement from ªStep
3.Is the measured resistance within the acceptable range? v If yes, replace switch power supply 2.
a. Go to ªStep
vIf no, the problem is in the switch supervisor card. a. Go to ªStep
Step
You arrived at this step because you received a ª...fanfail...º message or you found a problem with the switch supervisor control cable
1.One or more of the following conditions exist:
v Warning Fan: ªfanwarning1º, ªfanwarning2º, ..., ªfanwarning5º
v Shutdown Fan: ªfanfail1º, ªfanfail2º, ..., ªfanfail5º
2.Have customer remove the SP Switch from the active configuration and power off the SP Switch.
3.Set switch circuit breaker to the Off position.
4.Unplug cables connected to J1 and J2 at the rear of the SP Switch.
5.Remove the front panel assembly from the inner chassis.
6.Use Table
Chapter 1. Maintenance Analysis Procedures (MAPs)