GEM0650/0956/1256 Remote

Operation: Refrigeration

Low Condensing Temperature

The refrigeration system under low condenser air temperatures is much the same as it is under higher temperatures, with the exception that the resulting low head pressures cause the head pressure control to close off the liquid line between the condenser and the receiver.

This forces more refrigerant into the condenser (with a small amount of discharge gas going into the receiver to maintain pressure until the head pressure is built back up to 180 PSIG). At that pressure the valve opens up the liquid line from the condenser to the receiver.

Refrigeration Schematic

Remote Condenser

Discharge

Liquid Line

Line

Detail of Head Pressure Control Valve

Liquid Line Valve

Thermostatic Expansion Valve

Head Pressure

Control Valve

Evaporator

Receiver

 

Compressor

 

 

 

 

Suction Line

 

 

 

 

 

 

 

 

 

 

 