TROUBLESHOOTING SECTION

WARNING: Inspection, testing and repair of electrical equipment should only be performed by a qualified service techni- cian. Many of the tests require that the unit have power to it and live electrical components be exposed.

USE EXTREME CAUTION WHEN TESTING THE MACHINE.

 

 

 

 

 

 

Symptom

Possible Cause

Action

 

 

 

 

 

 

 

Green LED flashes, but no ignition (igniter

Gas flow interrupted.

Check manual gas valve is open.

 

 

sparks, no gas).

 

 

 

 

 

 

 

 

 

 

 

Check regulated gas pressure. (7.0 -10.5

 

 

 

 

WCI for natural gas or 11.0 - 14.0 WCI for

 

 

 

 

propane)

 

 

 

 

 

 

 

 

 

If gas line diameter is less than 1/2" or gas

 

 

 

 

line greater than 16 feet, reduce pressure

 

 

 

 

may result.

 

 

 

 

 

 

 

 

Combination gas cutoff valve is closed.

Ensure 12 VDC to both sides of valve. If

 

 

 

 

not, check ECO and DSI. If yes, valve may

 

 

 

 

have failed shut. Replace valve.

 

 

 

 

 

 

 

 

Modulating valve forced out of normal range

Tap on gas supply line between the

 

 

 

and may be stuck (common occurrence

combination cutoff valve and the modulating

 

 

 

during shipment).

valve. This tapping helps to free the piston.

 

 

 

 

 

 

 

Green LED flashes, but no ignition (no

Ignition wire loose or broken.

Check wire for continuity. Check connection

 

 

igniter sparks, gas flow and smell present).

 

to both the DSI and spark probe.

 

 

 

 

 

 

 

 

Improper gap on spark probe.

Check height of probe above burner (should

 

 

 

 

be 1/8"). Check gap between probe ends

 

 

 

 

(1/8"). Ensure probe is not touching burner.

 

 

 

 

 

 

 

 

Defective DSI.

Disconnect ignition wire from DSI spade

 

 

 

 

connector. During ignition, a spark should

 

 

 

 

be seen at this spade. If none, replace DSI.

 

 

 

 

If spark exists, replace ignition wire.

 

 

 

 

 

 

 

The unit ignites, but will not rise above

Improper operation of modulating valve.

Check voltage to modulating valve. If

 

 

ignition burn.

 

greater than 2.0 VDC, modulating valve may

 

 

 

 

have been forced out of its operating range.

 

 

 

 

Tap on gas supply line between the

 

 

 

 

combination cutoff valve and the modulating

 

 

 

 

valve. This tapping helps to free the piston.

 

 

 

 

If less than 2.0 VDC, replace control board.

 

 

 

 

 

 