INSTALLATION
Specifications and Sizing of the Steam Generator for the Room
| Generator Power | Size of Enclosure | |
| Required | Rating at Voltage | (cubic feet) |
|
|
|
|
STEAMPRO | 240 VAC 30 AMP 3 WIRE (#10) | 5.0 kW@240 |
|
240/5 |
|
|
|
|
|
| |
S064000 | 208 VAC 30 AMP 3 WIRE (#10) | 3.75 kW@208 | |
|
|
|
|
STEAMPRO | 240 VAC 40 AMP 3 WIRE (#8) | 7.0 kW@240 |
|
240/7 |
|
|
|
|
|
| |
S062000 | 208 VAC 40 AMP 3 WIRE (#8) | 5.25 kW@208 | |
|
|
|
|
STEAMPRO | 240 VAC 60 AMP 3 WIRE (#6) | 10.0 kW@240 |
|
240/10 |
|
|
|
|
|
| |
S060000 | 208 VAC 60 AMP 3 WIRE (#6) | 7.5 kW@208 | |
|
|
|
|
How to Select Generator Size
Step 1. Determine cubic footage of steam enclosure: multiply LENGTH inches x WIDTH inches x HEIGHT inches to find cubic inches. Divide cubic inches by 1728 to determine cubic feet.
Step 2. Find steam enclosure size within the ranges shown on the chart for the supply voltage (240 VAC or 208 VAC).
Step 3. Consider material and climate: If the steam enclosure is constructed of tile or marble or if the steam enclosure is against poorly insulated outside walls in a cold climate, select the next higher or highest kW size of steam generator available. Natural stone such as marble may reduce the cubic cpacity by as much as 50%.
Electrical Requirements
All SteamPro generators operate at 208 or 220 to 240 VAC at 50 or 60 Hz. Circuit is to be single phase
Caution: Without proper grounding and bonding, a system malfunction may cause fatal shock.
2