Kenmore 153.335943 Installation Instructions contd, The vent piping can be inst led as follows

Models: 153.335943 153.335863 153.335963 153.335846

1 44
Download 44 pages 60.48 Kb
Page 18
Image 18
The vent piping can be inst_led as follows:

Installation Instructions (cont'd)

VENTING SYSTEM EXAMPLE INSTALLATIONS FOR ALL MODELS

The vent piping cannot under any circumstances be run down- hill.

The vent piping can be inst_led as follows:

1. No more than 3 elbows can be used.

2. Horizontal runs require a minimum V,,"rise per foot.

35'MAX. 16" MIN,

13" MIN.

MIN.

MIN. RISE ¼"

I1"

PERFOOT

 

 

3.The total vertical and horizontal run cannot exceed 35'

for 3" vent piping (20' maximum if 2" vent piping is _:se_ on 40,000 BTU/Hr. models) with a maximum of three 90 ° elbows.

MIN. RISE¼"

MAX.

MIN. RISE I/4"

PER FOOT

MAX. 3

MIN. RISE 1/4"

PERFOOT

ONE ELBOW

PERFOOT

MIN. RISE ¼"

PERFOOT

MIN. RISE }/4"

PER FOOT

MIN. RISE¼"

PERFOOT

I

18

Page 18
Image 18
Kenmore 153.335943, 153.335863, 153.335846 Installation Instructions contd, The vent piping can be inst led as follows