Kenmore 153.336262 Gas Piping, Fire and Expmosion Hazard, Do not store corrosive chemicals

Models: 153336762 153336362 153336466 153.336962 153.336262 153336566 153336862 153336162

1 32
Download 32 pages 19.76 Kb
Page 16
Image 16
FIGURE18.

VENT TO OUTDOORS

OR. OHOMH'_Y

DRAFT HOOD

Be sure vent pipe is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation.

Chemical vapor corrosion of the flue and vent system may

occur if air for combustion contains certain chemical vapors.

Spray can propellants, cleaning solvents, refrigerator and air

conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.

FIGURE 17.

The vent pipe from the water heater must be no less than the diameter of the draft hood outlet on the water heater and must

slope upward at least 1/4 inch per linear foot (21 mm per meter), see Figure 18.

TO

CHmMNEY

FIGURE18.

All vent gases must be completely vented to the outdoors of the

structure (dwelling). Install only the draft hood provided with the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal

SCreWS.

There must be a minimum of 6 inches (153 mm) clearance

between single wall vent pipe and any combustible material. Fill and sea! any clearance between single wal! vent pipe and

combustible material with mortar mix, cement, or other

noncombustible substance. For other than single wall, follow

vent pipe manufacturer's clearance specifications. To insure a tight fit of the vent pipe in a brick chimney, seal around the vent pipe with mortar mix cement.

• Flue gases may escape if vent pipe is not connected

-Do not store corrosive chemicals

in vicinity of water heater.

• Chemical corrosion of flue and vent system can cause serious injury or death

-Contact a qualified instalbr or service agency.

Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.

Failure to have required clearances between vent piping and

combustible material will result in a fire hazard.

Gas Piping

Fire and Expmosion Hazard

Do not use water heater with any gas other than the gas shown on the rating plate.

Excessive pressure to gas control valve can cause serious

injury or death

Turn off gas lines during installation

Contact qualified installer or service agency

Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (3.5kPa) for natural and propane gas

(L.R). The minimum inlet gas pressure listed on the rating

plate is for the purpose of input adjustment. If the gas control valve is subjected to pressures exceeding 1/2 pound per square inch (3.5kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.

If the main gas line shut-off serving all gas appliances is used,

also turn "OFF" the gas at each appliance. Leave all gas

appliances shut "OFF" until the water heater installation is complete.

A gas line of sufficient size must be run to the water heater. Consult the current edition of National Fuel Gas Code ANSI

Z223.1/NFPA 54 and your gas supplier concerning pipe size.

There must be:

*A readily accessible manual shut off valve in the gas supply line serving the water heater, and

*A drip leg (sediment trap) ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve.

*A flexible gas connector or a ground joint union between the shut off valve and control valve to permit servicing of the unit.

Be sure to check al! the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.

The minimum inlet gas pressure shown on the rating plate is that which will permit firing at the rated input.

16

Page 16
Image 16
Kenmore 153.336262 Gas Piping, Fire and Expmosion Hazard, Do not store corrosive chemicals, in vicinity of water heater